Analytical Method for Energy Storage Sizing and Reliability Assessment for Power Systems with Variable Generation
Files
Date
2020-01-07
Contributor
Advisor
Department
Instructor
Depositor
Speaker
Researcher
Consultant
Interviewer
Narrator
Transcriber
Annotator
Journal Title
Journal ISSN
Volume Title
Publisher
Volume
Number/Issue
Starting Page
Ending Page
Alternative Title
Abstract
This paper presents a mixed integer linear program (MILP) to optimally size power and energy of energy storage systems (ESSs). The sizing model takes into account conventional generation (CG) operation constraints in addition to seasonal and locational wind speed and solar radiation variations, and variable generation (wind turbine systems (WTSs) and solar cell generators (SCGs)) forced outages. Subsequently, the outcomes of the ESS sizing model are inputted to the probabilistic production method (PCC) to assess the reliability of the integrated system. All aforementioned analyses have been applied to a system with different penetration levels. The method is demonstrated with case studies on a system consisting of 10 CG units and VG penetration levels of 20% and 30%. For each penetration level, ESS sizing is computed and then reliability assessment is performed.
Description
Keywords
Distributed, Renewable, and Mobile Resources, energy storage systems, expected unserved energy, loss of load probability, mixed integer linear programming, probabilistic production costing.
Citation
Extent
10 pages
Format
Geographic Location
Time Period
Related To
Proceedings of the 53rd Hawaii International Conference on System Sciences